High Voltage Electrical Glove with High Mechanical Resistance Without Leather Overglass

Brand Name

Regeltex

Model No.

Class 00-04

Feature/ Overview

Class 00 – 04

Max operating voltage (volts): 500 -36000

Proof test voltage (volts) 2500 – 40000

Withstand voltage (volts) 5000 – 50000

 

Description

full range of insulating gloves for live working complies with the specifications of the European standard EN 60903:2003 and the international standard IEC 60903:2002.

Likewise, our production is subjected to a system for ensuring EC quality of production by means of monitoring to implement article 11b of the 89/686/EEC directive relating to Personal Protective Equipment which classifies insulating gloves for live working in category III (mortal risks).

Summary table

Class

Lengths available

Categories

Thickness

in mm *

Sizes available

Colour of packaging

00

28/36 cm

AZC

0.5

8-9-10-11

Beige

0

36/41 cm

AZC

1.0

8-9-10-11

Red

1

36/41 cm

AZC

1.5

8-9-10-11

White

2

36/41 cm

RC

2.3

8-9-10-11

Yellow

3

36/41 cm

RC

2.9

8-9-10-11

Green

4

41 cm

RC

3.6

9-10-11

Orange

*Obtaining the category authorises an additional thickness of O.6mm
Signification of category letters :
A : Acid – Z : Ozone – H : Oil – C : Very low temperatures – R : A+Z+H

Electrical requirements (routine test and sampling test in alternating current)

Class

Max operating voltage (volts)

Proof test voltage (volts)

Withstand voltage (volts)

00

500

2 500

5 000

0

1 000

5 000

10 000

1

7 500

10 000

20 000

2

17 000

20 000

30 000

3

26 500

30 000

40 000

4

36 000

40 000

50 000

  1. ln the choice of class, it is important to define the network nominal voltage which must not exceed the maximum operating voltage. For multiphase networks, the network nominal voltage is the voltage between phases.
  2. The test voltage is the one applied to gloves during the individual routine tests.
  3. The withstand voltage is the one applied during the validation tests after the gloves have been conditioned for 16 hours in water and after a 3-minutes test at the proof voltage.